| ROOF HUGGER ENGINEERING AND TECHNICAL INFORMATION |
|
FLORIDA PRODUCT APPROVED
INSTALLATION GUIDE
Click PDF for an Adobe PDF file for viewing or click CAD for downloading a CAD file
SYSTEM 1:
FLORIDA PRODUCT APPROVAL # 9561.1, 10141.0
Existing Roof Panel: “R” panel (26, 24, 22 ga.)
New Roof Panel: “PBR” panel 12” o.c. rib spacing, 26 or 24 gauge.
New Roof Panel Attachment: 1- #12–14 Tek-3 WeatherGuard fastener every 12” (12”-12”-12”…) into sub-purlins, Lap Fasteners ¼”–14, 20” o.c.
Roof Hugger Sub- Purlin Spacing: 5’-0” o.c. (Eave and every purlin line)
Roof Hugger Attachment: 2- #12–14 Tek-3 fasteners per L.F. into existing purlin. |
SYSTEM 1 - ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
L / 120 |
L / 180 |
L / 240 |
26 |
40.00 |
40.00 |
38.00 |
24 |
35.00 |
31.44 |
26.42 |
SYSTEM 2:
FLORIDA PRODUCT APPROVAL # 9561.1, 10141.0
Existing Roof Panel: “R” panel (26, 24, 22 ga.)
New Roof Panel: “PBR” panel 12” o.c. rib spacing, 26 or 24 gauge.
New Roof Panel Attachment: 2 - #12-14 Tek-3.
WeatherGuard fastener every 12” (7”-5”-7”-5”-7”…) into sub-purlins, Lap Fasteners ¼”–14, 20” o.c.
Roof Hugger Sub-Purlin Spacing: 5’-0” o.c. (Eave and every purlin line).
Roof Hugger Attachment: 2- #12–14 Tek-3 fasteners per L.F. into existing purlin. |
SYSTEM 2 -
ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
L / 120 |
L / 180 |
L / 240 |
26 |
65.00 |
45.00 |
33.80 |
24 |
60.00 |
60.44 |
58.14 |
SYSTEM 3:
FLORIDA PRODUCT APPROVAL # 9561.1, 10141.0
Existing Roof Panel: R panel (26, 24, 22 ga.)
New Roof Panel: PBR panel 12 o.c. rib spacing, 26 or 24 gauge.
New Roof Panel Attachment: 2- #1214 Tek-3 WeatherGuard fastener every 12 (7-5-7-5-7
) into sub-purlins, Lap Fasteners Ό14, 20 o.c.
Sub-Rafter Spacing: 2-0 o.c.
Roof Hugger Sub-Purlin Spacing: 5-0 o.c. (Eave and every purlin line). 2-6 o.c. or less over sub-rafters between primary purlins.
Roof Hugger Attachment: 2- #1214 Tek-3 fasteners per L.F. into existing purlin, 2- Ό-14 Tek-3 into sub-rafter (1 each side of major ribs), 2-#17 into existing roof panel (1 each side of major ribs) and 1- #10 Pancake Head fastener 2o.c. connecting Hugger to sub-rafter.
|
SYSTEM 3 - ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
L / 120 |
L / 180 |
L / 240 |
26 |
110.00 |
110.00 |
110.00 |
24 |
116.00 |
111.77 |
85.14 |
SYSTEM 4:
FLORIDA PRODUCT APPROVAL # 9561.1, 10141.0
|
Existing Roof Panel: R panel (26, 24, 22 ga.)
New Roof Panel: PBR panel 12 o.c. rib spacing, 26 or 24 gauge.
New Roof Panel Attachment: 2- #1214 Tek-3 WeatherGuard fastener every 12 (7-5-7-5-7
) into sub-purlins, Lap Fasteners Ό14, 20 o.c.
Sub-Rafter Spacing: 1-0 o.c.
Roof Hugger Sub-Purlin Spacing: 5-0 o.c. (Eave and every purlin line). 2-6 o.c. or less over sub-rafters between primary purlins.
Roof Hugger Attachment: 2- #1214 Tek-3 fasteners per L.F. into existing purlin, 2- Ό-14 Tek-3 into sub-rafter (1 each side of major ribs) and 1- #10 Pancake Head fastener 1o.c. connecting Hugger to sub-rafter.
|
SYSTEM 4 - ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
L / 120 |
L / 180 |
L / 240 |
26 |
140.00 |
140.00 |
116.17 |
24 |
145.00 |
120.41 |
92.24 |
SYSTEM 5:
FLORIDA PRODUCT APPROVAL # 9352.1
|
Existing Roof Panel: R panel (26, 24, 22 ga.)
New Roof Panel: 200 DL Standing Seam panel, 18 o.c. Rib spacing, 24 gauge, as Manufactured by Architectural Building Components, Houston, TX.
New Roof Panel Attachment: 2- #1/414 Tek-3 Fasteners into sub-purlins spaced 5-0 o.c.
Sub-Rafter Spacing: None.
Roof Hugger Sub-Purlin Spacing: 5-0 o.c. (Eave and every purlin line).
Roof Hugger Attachment: 2- #1214 Tek-3 fasteners per L.F. into existing purlin.
|
SYSTEM 5 - ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
Purlin Space |
Max. Load PSF |
24 |
5'-0" |
40.00 |
SYSTEM 6:
FLORIDA PRODUCT APPROVAL # 9352.1
|
Existing Roof Panel: R panel (26, 24, 22 ga.)
New Roof Panel: 200 DL Standing Seam panel, 18 o.c. Rib spacing, 24 gauge, as Manufactured by Architectural Building Components, Houston, TX.
New Roof Panel Attachment: 2- #1/414 Tek-3 Fasteners into sub-purlins spaced 5-0 o.c.
Sub-Rafter Spacing: 2-0 o.c.
Roof Hugger Sub-Purlin Spacing: 5-0 o.c. (Eave and every purlin line). 2-6 o.c. over sub-rafters between primary purlins.
Roof Hugger Attachment: 2- #1214 Tek-3 fasteners per L.F. into existing purlin, 2- Ό-14 Tek-3 into sub-rafter (1 each side of major ribs), 2-#17 into existing roof panel (1 each side of major ribs) and 1- #10 Pancake Head fastener 2o.c. connecting Hugger to sub-rafter.
|
SYSTEM 6 - ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
Purlin Space |
Max. Load PSF |
24 |
2'-6" |
80.00 |
SYSTEM 7:
FLORIDA PRODUCT APPROVAL # 9352.1
|
Existing Roof Panel: R panel (26, 24, 22 ga.)
New Roof Panel: 200 DL Standing Seam panel, 18 o.c. Rib spacing, 24 gauge, as Manufactured by Architectural Building Components, Houston, TX.
New Roof Panel Attachment: 2- #1/414 Tek-3 Fasteners into sub-purlins spaced 5-0 o.c.
Sub-Rafter Spacing: 2-0 o.c.
Roof Hugger Sub-Purlin Spacing: 5-0 o.c. (Eave and every purlin line). 1-3 o.c. over sub-rafters between primary purlins.
Roof Hugger Attachment: 2- #1214 Tek-3 fasteners per L.F. into existing purlin, 2- Ό-14 Tek-3 into sub-rafter (1 each side of major ribs), 2-#17 into existing roof panel (1 each side of major ribs) and 1- #10 Pancake Head fastener 2o.c. connecting Hugger to sub-rafter.
|
SYSTEM 7 - ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
Purlin Space |
Max. Load PSF |
24 |
1'-3" |
90.00 |
SYSTEM 8:
FLORIDA PRODUCT APPROVAL # 9352.2
|
Existing Roof Panel: R panel (26, 24, 22 ga.)
New Roof Panel: SuperLok, 16 o.c. Rib spacing, 24 gauge, as Manufactured by MBCI, Houston, TX.
New Roof Panel Attachment: 2- #1/414 Tek-3 Fasteners into sub-purlins spaced 5-0 o.c.
Sub-Rafter Spacing: None.
Roof Hugger Sub-Purlin Spacing: 5-0 o.c. (Eave and every purlin line).
Roof Hugger Attachment: 2- #1214 Tek-3 fasteners per L.F. into existing purlin. |
SYSTEM 8 - ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
Purlin Space |
Max. Load PSF |
24 |
5'-0" |
47.50 |
SYSTEM 9:
FLORIDA PRODUCT APPROVAL # 9352.2
|
Existing Roof Panel: R panel (26, 24, 22 ga.)
New Roof Panel: SuperLok, 16 o.c. Rib spacing, 24 gauge, as Manufactured by MBCI, Houston, TX.
New Roof Panel Attachment: 2- #1/414 Tek-3 Fasteners into sub-purlins spaced 5-0 o.c.
Sub-Rafter Spacing: 2-0 o.c.
Roof Hugger Sub-Purlin Spacing: 5-0 o.c. (Eave and every purlin line). 2-6 o.c. over sub-rafters between primary purlins.
Roof Hugger Attachment: 2- #1214 Tek-3 fasteners per L.F. into existing purlin, 2- Ό-14 Tek-3 into sub-rafter (1 each side of major ribs), 2-#17 into existing roof panel (1 each side of major ribs) and 1- #10 Pancake Head fastener 2o.c. connecting Hugger to sub-rafter. |
SYSTEM 9 - ALLOWABLE DESIGN PRESSURES (-PSF)
FACTOR OF SAFETY 2.0
Panel Ga. |
Purlin Space |
Max. Load PSF |
24 |
2'-6" |
80.00 |
|